Answers:
- Absolutely not! We recommend that,
where possible, you leave the charger plugged in and switched on, with
the batteries connected, until you next need the battery for use.
There are several reasons for this. At the end
of the charge cycle, when the green ready light is on, the charger is
trickle charging the battery in constant voltage float/standby mode,
nominally at 2.3 Volts per cell. This is the same charge method used
for batteries in standby applications such as alarm panels or emergency
lighting, where the battery is intended to be charged 24 hours a day,
every day. At this voltage, the battery will not be gassing so loss
of electrolyte is minimal. The charge current drops exponentially to
a very low level, sufficient to maintain the battery in a fully charged
state and to compensate for any self discharge. Over time this low rate
of charge will tend to equalise charge imbalance between the cells,
which can extend the battery life.
By leaving the charger switched on, you will prevent any risk of damage
to the battery from sulphation (which can be caused by allowing the
battery to stand in the discharged state). The energy consumed in standby
mode is minimal, typically about 10 Watts for a medium size charger,
so one unit (One KWHr) of electricity is used every 100 hours, which
costs about one and a half pence per day. The only exception to this
recommendation is in cases where the battery manufacturer specifically
states that the battery is not suitable for constant voltage float operation,
or when running from an intermittent AC supply such as a generator.
- Well, the lower
cost charger may be fine for some applications. But, if you are using
a battery in a demanding application where performance and battery lifetime
are important, you might find that saving money on the battery charger
is not cost effective in the long term.
If the battery is overcharged or undercharged then your product will
not perform as well as it could, and the battery will not give the lifetime,
in terms of cycles of discharge and standby time, and so will need to
be replaced more frequently than you, or your customers, were expecting.
Batteries can fail within the warranty period, and the battery manufacturer
may decline warranty claims for replacement batteries where incorrect
charging has contributed to the problem. This is why it’s advisable
to test your system carefully using the exact battery, charger and load
in a simulation of actual use.
Also, the system designer should ensure that the cyclic and float voltage
settings of the charger are within the ranges specified by the battery
manufacturer. Our chargers are designed to offer the best battery performance
and lifetime with features such as three stage charging, precise voltage
regulation, proportional timing, overrun timer, low start voltage, and
low parasitic loading. Some of our regular customers started using our
product only after they had experienced a problem. Don’t find
this out the hard way - there is much more to the specification of a
battery charger than the Voltage, Current rating, and price.
- A battery charger is a type
of DC power supply unit (PSU) which is specifically designed for charging
batteries. While any DC PSU can be used to charge batteries, there are
serious potential pitfalls to using a generic PSU as a battery charger.
For example, a DC PSU may include regulation circuits, which may be
damaged if a battery is connected to the output, before the AC PSU is
switched on. The regulation circuit in a power supply is not designed
to reduce parasitic load and so may draw power from the battery if left
connected when AC power is switched off.
These two issues can be addressed by adding a blocking diode, but then
the volt drop of the diode (which is temperature dependant) needs to
be allowed for. Generic PSUs do not provide multiple stage charging
with different voltage limits, or temperature compensation of the charge
voltage, or reverse battery connection protection. In general, it’s
better to use a battery charger that was designed for the job, rather
than a general purpose DC PSU, for battery charging. If using our chargers,
there is no need to fit any external blocking diode or contractor to
prevent current flow from the battery back into the charger, when the
AC supply is off, as may be required with some generic power supplies.
- No, we don’t offer that
type of charge termination. We use an alternative technique called proportional
timing, which does the same thing, but does it better.
We have done extensive testing on different types and sizes of batteries
to reach this conclusion. Many competitors multi stage chargers use
a current comparator to determine when to switch from bulk charge (constant
voltage at the cyclic voltage limit)to float/standby mode (constant
voltage at the float voltage limit). This method, although widely used,
has some drawbacks. The problem is that the current at end of charge
varies with a number of parameters external to the charger, such as
the temperature, the age of the battery, and the size of the battery.
In a constant voltage charge system, the charge current falls off exponentially
as the battery EMF increases and the charger voltage is held constant.
At the end of the charge, where the determination of switch to float
has to be made, the slope of the current against time graph is quite
flat, so a small change in the current setting can make a wide difference
to the charge time. When a battery approaches the end of it’s
life it tends to draw a higher self discharge current due to sludge
accumulation increasing electrical leakage between the plates, so if
a current comparator is used the charger may never switch down to the
float/standby voltage, resulting in overcharge, gas emission, and premature
battery replacement. Our chargers use proportional timing where the
switch to float is timed optimally, eliminating the need for sensing
low currents, and eliminating adjustments to the charge termination
controller to match the Amp-hour size of the specific battery.
- Probably not. Our chargers
feature short circuit and reverse polarity shutdown, so they don’t
produce any output voltage unless they are actually connected to a battery.
The charger waits to "sense" the battery voltage on the output
before it starts producing voltage, so you cannot test for DC output
with a volt meter or test lamp, when there is no battery connected to
the charger output. Try switching the AC supply to the charger off and
on, the LED indicators should show the power on test sequence (Green-Yellow-Red,
each for about a half second) each time the AC power is applied. If
there is no LED test indication, check that AC input power is getting
to the charger, and the AC Power input fuse is intact. If the LED power-on
indication is OK, try connecting the charger to a known good battery
(of the correct voltage, but almost any size will do for testing), the
yellow charge indicator should come on, and the battery voltage should
rise to around 2.4 Volts/Cell. If this happens, the charger is producing
output. If the yellow charge LED does not come on, when the battery
and AC power are connected, check carefully that your connections from
the charger to the battery are sound and that the battery is wired the
correct way around (Red lead from charger to the battery Positive).
If the battery is very excessively discharged (to less than 1 or 2 Volts
DC in total) then the charger may not start because it can’t detect
that the battery is there. If this happens, try removing the DC load
to allow the battery voltage to recover, or connect another battery
in parallel momentarily to provide starting bias. Note that batteries
discharged to zero voltage are liable to be damaged by sulphation if
allowed to remain in a discharged state for more than a few hours.
- SCR controlled chargers have
un-smoothed output, so the DC output to the battery is in the form of
a pulse of current each half cycle of the AC supply. During the time
when the AC input is crossing zero, in between pulses of output, there
is no current flowing in the cables from the charger to the battery.
We take advantage of that, by using a sample-and-hold circuit to measure
the battery voltage at mains zero crossing, so that the charger can
monitor the battery voltage without errors that would otherwise be caused
by volt drop on the DC cables. When in Constant Voltage mode, the charger
will maintain a constant voltage at the battery terminals, by increasing
the voltage at the charger end of the cable if needed to compensate
for volt drop in the cable. In some applications, especially when using
long DC cables, this feature can improve performance and eliminate the
requirement to run separate voltage sensing leads. This feature does
not apply to switch mode or other smoothed output chargers.
- The override (sometimes called
overrun) timer is a software timer, which starts at each beginning of
each charge, and runs until the green “Ready" light comes
on. There is a fixed maximum time allowed for completion of each charge
cycle, the default setting is 18 hours, but this setting can be modified
if required by changing the software. If the override timer times out
before the “Ready" LED comes on, the unit enters “fault
mode" and shuts down, producing no further output. The fault mode
is indicated by a continuous rapid flashing of the Green “Ready"
LED. The fault mode can be cleared by either switching the AC supply
off and on, or by disconnecting from the battery. Note that, providing
the charge cycle completes normally, the charger will normally remain
in float/standby mode with the green LED on, and 2.3V/Cell constant
voltage output, indefinitely because the override timer is stopped when
the green “Ready" LED comes on. The override timer is intended
to prevent continuous charging (and possibly overcharging) under fault
conditions, such as a shorted cell in the battery, or a charger fault
causing low output current, or a voltage sensing failure. For very unusual
applications, if a charger is used on a disproportionately large battery
(such as sometimes used in a float/standby application) where the charger
may normally take over 18 hours to reach the end of the charge cycle,
we can supply a modified control chip with the override timer disabled
(-NT option). Normally, even in float/standby applications, the charger
current rating should be selected so that it is large enough to fully
recharge the battery in less than 18 hours, so the override timer will
never terminate the charge under normal conditions.
- Parasitic loading means the
DC current that flows into the charger from the battery when there is
no AC power supply to the charger. In some competitors units the control
circuits in the charger are powered from the DC output circuit, so that
the charger may “leak" several tens of milliamps (or sometimes
more) back out of the battery, if it’s left connected when there
is no AC power, or when it’s switched off. This can cause a problem
in applications where the charger is normally, or may be, left wired
to the battery, when the AC input power is switched off or the supply
fails. A load of just 50mA will discharge the battery by 1.2 Ah every
20 Hours, and by 8.4 Ah in a week. If , over time, the battery becomes
over-discharged, that can lead to sulphation, or excessively low voltage,
so that when the AC power is restored, the battery will not recharge
even though power is available. Ideally, the charger should be specified
so that the parasitic loading is less than, or comparable to, the battery
self discharge rate. Our chargers typically have a parasitic load spec
of less than 300 micro Amps, or 0.3 mA, which is low enough to be insignificant
in normal applications. No series isolation diode between charger and
battery is needed when using chargers with a low parasitic load current.
- This could be due to a number
of things, because the battery, the load, and the charger have to work
together as a system, so a problem in any one of them may result in
sub-optimal performance. First, review answer to “How long will
my battery support my load, how can I calculate the expected runtime?"
below and check the expected runtime of the load current against the
size of the battery. Measure the actual load current and verify that
it is as expected. Check the “Cyclic Voltage Limit" and “Float/Standby
Voltage Limit" settings of the charger are correct per the recommendations
of the manufacturer of your battery. For details on how to check these
voltage settings, see answer “How does one check and adjust the
Voltage settings of my battery charger?" below. If the voltage
settings are OK, try leaving the battery on charge for an extended period
(for example, over the weekend) to make sure it’s as fully charged
as possible. Also see answer to “How does one check and adjust
the Current Limit setting of my battery charger?" to confirm that
the current output of the charger is up to specification. In the cables
from the charger to the battery, check that there are no excessively
long cables, thin wiring, or badly connected terminals causing power
loss in the cable run, verify the charge current flowing using an Amp
meter connected in series with the battery terminal under the actual
conditions of typical charging. If the charger voltage or current values
are not correct, either adjust them or return the charger for repair.
Consider having the battery capacity tested using a constant current
test load, if you have access to one, typically a good battery will
run a 1xC rate discharge for 30 minutes to 1.5V/Cell, for example, a
32Amp-hour battery, discharged at 32 Amps, should run for 30 minutes
before the battery terminal voltage drops to below 9 Volts. The runtime
of the battery drops over time, a good quality equipment battery will
typically provide 200 cycles of discharge, to 100% depth of discharge,
before needing replacement. These figures are typical, check the published
spec from the battery manufacturer for the exact type of battery you
are using.
- This can be due to a number
of things. If the battery has a faulty cell, then it’s on charge
voltage will not reach the charger set point to switch to Constant Voltage
Mode, which results in overcharging of the remaining cells, until the
overrun timer terminates charge after 18 hours. If there’s a fault
in the charger which causes the voltage setting to drift upwards, or
if the charger is not set for the correct battery type, that can cause
overcharging. In any case, the appropriate test, is to measure the battery
voltage when in the constant voltage charge stage, and confirm that
the voltage is correct per the specification of the battery. To do this,
switch the charger off and on to reset it, and then wait until the “charge"
light starts to flash (or, on some units, until the “80%"
LED comes on. The charger is now in the constant voltage mode. Measure
the battery voltage using an accurate digital volt meter, measuring
at the battery terminals. If the voltage is too high (for example, more
than about 14.7V on a 12V, absorbed electrolyte sealed battery, then
the charger is faulty or needs adjustment. In some very unusual applications,
if the AC power supply is unreliable (frequent supply interruptions)
that may result in overcharging, because the proportional timer always
holds the battery at the cyclic charge voltage limit for a minimum of
one hour before switching back to float/standby. If the battery is supporting
a load while charging, and the nature of the load is regular, high current
demand pulses (greater than the charger current rating),that may reset
the proportional timer and cause overcharging. In this case, the charger
can be modified to eliminate the 1 hour minimum time offset, contact
the factory if this modification is needed in your application.
- Yes, but there are a few
points to watch for. Firstly, the load will be subjected to the on-charge
voltage of the battery, which is of necessity somewhat higher than the
battery’s normal on load voltage. For example, a 24 Volt battery
system will normally be held at about 29 Volts DC for several hours
during the Constant Voltage charge stage, so you should check that your
DC load is specified to be OK at the higher voltage, including some
allowance for voltage overshoot and charger adjustment tolerance. If
it looks like there might be a problem, consider lowering the charger
cyclic voltage adjustment setting (this will result in a longer recharge
time but will reduce the stress on the load). Or consider using a voltage
regulator, or voltage reducer, between the battery and the load. Secondly,
any load current drawn from the battery while charging, will reduce
the effective charge current and so extend the recharge time. It’s
best to keep the average level of DC load current to not more than about
20% of the charger current rating, for this reason. Thirdly, if the
charger is an un-smoothed SCR type, it will cause superimposed AC ripple
on the battery DC output, which can upset sensitive electronic loads,
for example causing a background hum noise on radios. This can be reduced
by keeping the charger cables and the load cables separate if possible
– run the charger cables (both Positive and Negative) directly
to the battery terminals, separate from any other wiring. Alternately,
a DC filter circuit can be added to the charger output.
- Charging more than one battery,
or battery pack, from a single charger, is something of a compromise
and should be avoided if possible. It’s much better to use two
smaller chargers, one for each battery. We also offer “bank"
chargers which include several independent charging circuits. If the
batteries are not equally discharged, that is if they support different
loads, then it’s not possible to charge them optimally using one
charger, because the timing of the stages of charging should be matched
to the battery depth of discharge for optimal charging performance.
But, this is often done, for example in a boat or RV/caravan application
where there is a “starting" battery and a “house"
battery, and it’s desired to charge both from a single battery
charger. A common arrangement is to use a “diode splitter"
to divide the charger output between the two batteries, while maintaining
isolation between the batteries, so that, for example if the “house"
battery gets discharged, the vehicle can still be started. Our chargers
are designed to be connected directly to the battery, they will not
operate correctly, if there is a diode splitter fitted between the charger
and the battery, because the diode does not allow reverse current flow
from the battery to the charger so the charger cannot measure the battery
voltage accurately. To get around this, we suggest fitting a 1K Ohm,
half watt, resistor across each of the diodes. This is a readily available
component, and it will allow enough current to pass through the diode
to allow the charger to operate normally. If more than one battery is
connected, it’s advisable to try to make the lengths and thickness
of the cable to each battery about the same so as to avoid unequal resistances.
Even so, the charger will measure the battery voltage as halfway between
the two actual voltages, if they are different, and so the charging
will not be as optimal as it should be. This is a fundamental problem
and the best solution is to fit a separate charger for each battery
bank. Charging batteries of multiple cells, either in series or in parallel,
to make a higher voltage or Amp-hour rating, is acceptable, providing
the batteries are of the exact same type, capacity, and age, and are
connected in series or parallel at all times so that there is no unequal
load. A common error, is to charge two 12V batteries in series with
a 24V charger, and then to “tap" a 12V supply from the centre
connection, this always results in one battery overcharged and the other
undercharged which shortens the life of both batteries, and so should
be avoided. It’s much better to use two 12V chargers, if there
is any load driven from the connection between the batteries.
- There are three preset pots
on the PCB inside the charger, these are marked as V-LIM1, V-LIM2/STBY,
and I-LIM. Some chargers also have a DIP switch for setting the battery
type. In any case, to check and adjust the charger voltage limits, proceed
as follows. First, connect the charger to a fully charged battery. The
battery used for this test can be a small one, or it can be the battery
normally used with the charger, but it must be in good condition, fully
charged and of the correct number of cells (for example, 12 cells for
a 24 Volt charger, or 6 cells for a 12 V charger, and so on. The test
battery does not have to be exactly the same type as the actual battery
used in the application. Connect a calibrated accurate digital volt
meter or multi-meter in parallel with the battery terminals. The volt
meter should be connected directly to the battery terminals if possible.
Switch the charger on and observe the green-yellow-red LED indication
(Power on self check) showing the circuit board appears to be working
OK. Then the Charging (usually yellow) LED should come on, indicating
that a battery is connected to the charger. After a few seconds, the
charger should reach the voltage limit and enter the constant voltage
stage of charge. This is indicated, either by the yellow charging LED
starting to flash off and on about once per second, or by the "80%
Charged" LED coming on, if fitted. (Some non standard chargers
do not flash the yellow charging LED to indicate when the voltage limit
is reached, but those are very unusual). When the charger is in constant
voltage mode, observe the volt meter reading. The reading should be
correct per the "cyclic charge voltage limit" for the type
of battery being used. The default setting, which works OK with most
batteries, is 14.5V (2.42 Volts per Cell). If the voltage is more than
0.1 Volt wrong, adjust the preset marked V-LIM 1 to get the correct
voltage. Next, locate the test point link on the PCB. On PCB's with
a 3-pin header, the test point is the 2 pins nearest the rear of the
unit. On PCB's with a 2-pin header marked "test", that is
the test point. Bridge the test point pins momentarily using a small
flat blade screw driver, and observe that the green "ready"
LED comes on and stays on. When the green LED is on, allow the battery
voltage to settle for a few seconds, then check the reading which should
be 13.8V on a 12V battery, or 2.3 Volts per cell. If necessary, adjust
using the preset pot marked as either "V-LIM 2" or "STBY"
(Standby). Note that, if the charger is fitted with temperature compensation
(usually there is a thermistor sticking out the side or rear in a pigtail
bush if this is fitted), then the voltage setting should be adjusted
to allow for the temp comp at the actual ambient temperature at time
of adjustment, if it is significantly different to 20 degrees C. The
temp comp adjustment is –0.004 Volts per cell per degree C difference
from 20C. For example a 12V (6 Cell) battery, if adjusted at 30C ambient
temperature, should be set to 0.24 Volts below the nominal setting,
so the float voltage would be 13.56V instead of 13.8V.
- The current limit setting
is adjusted using the preset pot marked "I-LIM" (short for
Current Limit). It is set when the charger is made and does not normally
need to be re adjusted. The current limit is a little more difficult
to check and adjust than the voltage limit, because the amp meter has
to be connected in series, and a load is required to hold the battery
voltage down. If you do need to check and adjust it, proceed as follows.
Connect the charger, either to a recently discharged battery in good
condition, or to any battery with a DC load in parallel that is draws
more current than the charger's current rating. For example, for adjusting
a 10 Amp charger, a 12 Amp DC Load would be suitable. A good current
load for small 12V chargers, is a car battery with the car headlamps
switched on, or a battery with a resistive or lamp load connected across
it. Connect an Amp meter in series with the charger output. Switch the
charger on, observe the current reading. It should correspond with the
charger nominal current rating. If the current is too high, adjust the
I-Lim preset to correct it. If the current is too low, and will not
adjust to the correct value, confirm that the AC input voltage is within
spec, and that the battery voltage when charging is around 2.1 Volts
per cell (approximately 12.6V on a 12V battery). The charger must be
in current limit when adjusting the I-Lim preset, or the adjustment
will have no effect. Note that the amp meter must be connected in series
with the charger output in such a way that it does not add any significant
amount of resistance, for example if using a digital multi meter, the
standard set of meter probes should not be used because they are relatively
long and thin, and may give a falsely low current reading. A pair of
substantial thick and short test leads with 4mm plugs to plug directly
into the amp meter should be used instead. A DC reading clamp meter
is ideal, if available. A moving pointer type of meter is best because
it reads arithmetic mean value, digital meters may not give the correct
reading when measuring un-smoothed DC current. Meters which read RMS
values should be avoided because the arithmetic mean value corresponds
to battery charging time, and this can be significantly lower than the
RMS or equivalent heating effect current, if there is superimposed AC
ripple present.
- On chargers that are fitted
with a Battery Type DIP switch inside on the PC Board, the charger can
be quickly configured for use with either gel cell, sealed lead acid,
or liquid electrolyte battery types. The difference is the cyclic voltage
limit setting (this is the first voltage limit, where the charger changes
to constant voltage mode, which happens when the battery reaches about
80% level of charge). The DIP switch setting also has a small effect
on the float/standby voltage. If in doubt, we suggest use of the default
normal setting, as that will give satisfactory performance with most
battery types, with a voltage limit of 14.5V (per 6 cells). The sealed
lead acid or normal setting is appropriate for absorbed electrolyte
or AGM batteries. The two switch levers are marked on the PCB next to
the switch, as N for normal and G for gel. The default (factory) setting,
unless otherwise specified, is the "Normal" or "SLA"
(Sealed Lead Acid) setting, referred to as normal. To set this mode,
the switch marked N should be on, and the switch marked G should be
off. The gel cell setting lowers the cyclic limit voltage to 14.1V (per
6 cells) and to select this, the switch marked G is on, and the switch
marked N is off. The liquid electrolyte battery setting increases the
cyclic voltage limit to 15.6V (per 6 cells) and to select this both
switches should be off. Note that, if the liquid electrolyte setting
is used, there will be significant gassing in the battery when approaching
full charge, if the charging is done indoors with limited ventilation,
it may be better to select the Normal/SLA setting instead, which will
give reduced gas emission, but will take longer to fully charge the
battery. The benefit of having the dip switch is that the setting can
be changed in the field without having to use a volt meter and test
battery, so it allows use of the one charger type with different sorts
of lead acid battery technology. The DIP switch is only fitted on the
larger units, on the smaller units that don’t have a switch, the
same effect can be obtained by manually adjusting the voltage limit
settings using a fully charged battery and volt meter, as described
elsewhere. If special or custom voltage settings are required, to suit
a specific application, that can usually be arranged providing the settings
are specified when ordering.
- To a first approximation,
to calculate how long the battery will run the load, just measure or
calculate the current that the load will draw when running, and divide
the battery Amp-Hour (Ah) capacity rating by the load current, to give
runtime in hours. This will be the runtime to 100% depth of discharge
(DOD) and should be de-rated by 20% to avoid over discharge. Note that
the battery capacity is expressed in Amp Hours (Ah), this is not the
same as any figure in Amps which is a unit of current flow. If a battery
supplier offers you a "100 Amp Battery" you might want to
avoid that supplier! It’s important that the system designer calculates
the maximum depth of discharge, because the battery will not give good
lifetime or the expected performance if it’s too small to support
the load. In a cyclic application, (meaning an application where the
battery is charged and discharged on a regular basis) the battery depth
of discharge should be limited to no more than about 80% of maximum,
in order to get a cost effective battery cycle life. For reliability
and good conservative engineering, it's advisable to use a large battery
with plenty of capacity, that way the depth of discharge will be low
and the battery will last a long time. But there are often commercial
pressures to keep the cost as low as possible, so the designer must
balance these carefully, and it may be necessary to calculate the run-time
accurately. There are, though, some complicating factors. The first
is de-rating the battery capacity to allow for the rate of discharge.
Battery de-rating is only needed when discharging at rates faster than
the rate at which the Ah is specified in the battery data sheet. The
battery capacity is rated in Ah by the battery manufacturer, and is
usually available from the battery data sheet. But, the higher the discharge
current, the less efficient the battery becomes, so the Ah available
is highest at a low discharge current, and needs to be de-rated to a
lower figure at higher levels of discharge. The battery manufacturer
does not know what current your load will draw, so they specify the
battery at a given discharge current, or over a specified time to discharge.
If they use a long (20 hour) discharge, that yields the highest figure
in Ah. Typically, equipment batteries (like SLA or Gel batteries) are
specified in Ah over a 20 Hour discharge. Large cyclic or traction batteries
are often specified in Ah over a 5 Hour discharge. In any case, there
should be a graph available from the battery maker showing actual capacity
against discharge current. Not all battery suppliers give this data
in the same way, and some don’t give it at all, so it can be difficult
to compare one battery against another. Batteries designed for automotive
use sometimes have their capacity rated in "reserve minutes"
meaning minutes at a constant load current, which can be converted into
a figure in Ah. If in doubt, contact the battery manufacturer, and ask
for clarification. For an extreme example, if a battery is discharged
in a half an hour, it will usually provide only half of it’s rated
20 hour Ah rating. Thus, a good quality 50Ah battery, fully charged
and in good condition, will supply a load that draws 50 Amps, for only
30 minutes. The same battery, would supply a load that draws 1 Amp,
for 50 Hours, or a load that supplies 2 Amps, for 25 hours. So, it’s
essential, if discharging at high rates, to consult the battery supplier’s
data, to determine the actual battery discharge capacity at the load
current you are using. The load current should be measured or calculated
accurately, since the load current determines the size and cost of the
battery and charger. In cases where the battery load will vary during
the discharge (for example, when driving a motor, where current is proportional
to torque) the calculations can get complicated, as the battery de-rating
factor should be applied to each value of load current. Another issue
is the end of discharge voltage, which again varies with discharge current.
Batteries are specified in Ah to a given end point voltage, typically
1.5 Volts per cell, or 9 Volts per nominal 12V pack of 6 cells, and
this may not be enough voltage to drive the load properly, in which
case the discharge time must be de-rated. Another factor to consider
is how conservative the battery supplier is with their specifications.
The battery industry is very competitive, and there are some manufacturers
who claim maximum or optimal figures for their battery, while others
may give minimum or guaranteed figures. Brand new batteries direct from
the factory, will typically have about a 10%reduced capacity for the
first few cycles of discharge as the plates are not fully “formed"
when the battery is new. Some makers allow for this in their figures
for Ah capacity, others do not. It’ certainly advisable, in any
case, for you to test your system (Charger, battery, and load) extensively
as part of the design process, to collect your own data and base your
claims to your own customers, on that.
- This can be calculated approximately
as follows. The recharge time in hours equals the battery capacity in
Ah, multiplied by the Depth of Discharge in %, multiplied by 0.8, multiplied
by 1.5, divided by 100 times the charger current rating in Amps, plus
one hour. For example, a 55Ah battery, discharged to 80%, on a 6-Amp
charger, would take about 9.8 hours. A 110 Ah battery, discharged to
50%, on a 10 Amp charger, would take about7.6 Hours. The battery reaches
80% recharge relatively quickly, the last 20% of the charge is done
in constant voltage mode where the current is dropping exponentially,
so it is charging more slowly, this is the reason for the 1.5 factor
and the plus one hour constant. Our chargers usually provide an indication
when the 80% level and switch to CV mode has been reached (either an
indicator LED marked 80%, or the Charge LED starts to flash) showing
that the battery could be used at this point, with some loss of run
time. At the end of the charge cycle, the Green Ready LED will show
that the battery is ready for use. It’s recommended to leave the
charger connected and switched on, if possible, even after the green
LED shows, as the charger is still supplying a small current in standby
mode, which tops off the charging process. The heating effect on the
battery is proportional to the square of the charge current, while the
recharge time is inversely proportional to the linear value of the charge
current.
- These are many different types of
Lead-Acid rechargeable battery, and there is some confusion. Quite often
customers refer to a battery as a “Gel Cell", when in fact
it’s another type of SLA battery. There is not much difference
in discharge performance, but there is often a difference in recharge
voltage limit. Sealed Lead Acid is a generic term for all lead acid
batteries which have fixed tops, so the electrolyte is supplied with
the battery when it’s manufactured, and it’s not intended
that the battery ever be opened or topped up in the field. These are
also sometimes known as “maintenance free" batteries. Sealed
Lead Acid (SLA) has become a popular generic term, and is widely used
in the industry. It’s actually a rather misleading term, since
all lead acid batteries must have vents to allow any excess gas pressure
to escape from the battery casing, especially if cells become overcharged
under fault conditions such as a shorted cell. Lead acid batteries should,
in general, never be charged in a completely sealed cabinet or enclosure,
for this reason. The terms “Valve regulated battery" or “Recombinant
battery" which some makers (more correctly) use instead of SLA,
but which do not seem to be very widely used. All types Valve regulated.
or Recombinant batteries, normally release very little or no gas during
charge and discharge, as they are designed to operate with a small positive
gas pressure inside the battery casing. These SLA battery types can
be further divided into “gel electrolyte" and “absorbed
electrolyte" types. The Gel cells have the acid electrolyte in
the form of a gel, the absorbed electrolyte type have the acid in liquid
form, trapped in a glass fibre mat between the plates. Absorbed electrolyte
batteries are also sometimes called AGM (Absorbed Glass Mat) batteries.
A possible advantage of a gel electrolyte may be that if the battery
plastic casing is damaged in transit or in an accident, the electrolyte
is not in liquid form and can’t run out of the battery and cause
further damage or corrosion. But a disadvantage may be that some gel
batteries are more easily damaged by overcharging, because gas bubbles
form in the gel and may push the electrolyte away from the plate surface,
permanently reducing the capacity. In all cases, it’s advisable
to check the battery manufacturer’s spec for the recommended constant
voltage charging voltage range, and check that the charger is set within
that range, to provide the best performance with the type of battery
used in the application. Usually battery makers specify two settings
for the charge voltage limit, a higher value for Cyclic (short term
charging) and a lower value for Float (long term charging). Usually
cyclic setting is around 2.45 Volts per cell (14.7V on a 12V battery),
and the float setting is around 2.3 V/Cell (13.8v on a 12V battery).
Our chargers use both of these settings (V-Lim 1 and V-Lim 2 settings)
to provide both fast recharge and long term maintenance charge.
|